--> UL PPE 2000 Volts G Type Three Conductors + Yellow & Bare Grds
Call us Now (800) 967-9147

UL PPE 2000 Volts / Type G Mining Cable Three Conductors + Yellow & Bare Grds



Philaflex 600/2000 Volts
G Type PPE

APPLICATION: For extreme environments and working conditions where maximum resistance to extreme temperatures, chemicals, oil, fuel, abrasion, and flex fatigue is needed. Philafin™ mining cables and power cables are designed for powering heavy duty equipment used in mining, cranes, construction, drilling rigs, ships, emergency hospital black outs, movie/stage lighting, submersible pump, undersea and military field operations. Philatron Wire & Cable is a mining cable manufacturer and all cables are made in the USA to high quality standards.

G Type 4 Conductors

G four conductors mining and portable cables
  • Philaflex Double Wall Cross Linked Polyolifin Rubber *
  • Extreme Desert to Artic Temperature Ranges: +125°C to – 60°C
  • Extremely Reliable and Not Effected by Direct Sunlight & Ozone
  • Extra Flexibility for Safer Handling
  • Chemicals, Oil, Fuel, Salt Water, Abrasion, & Crush Resistant
  • MSHA Approved – Philatron’s Certification Number: 7K-281151
  • Lead and Asbestos Free for Safer Environment
  • Extra Flexible Stranded Bare Annealed Copper
  • UL Listed Type PPE 2000 Volts 105°C Portable Power Cable
  • Meets National Electrical Code for Type W Cable Applications
Part
Number
Gauge/MCM
Size
Strands Insulation
Thickness(")
Jacket
Thickness(")
Ground
Size/Gauge
Cable
O.D.
Weight -
Lbs./1,000 feet
Ampacity*
G00064 6 62 x 34 Ga. 0.06 0.095 12 0.915 701 72
G00044 4 104 x 24 Ga. 0.06 0.095 10 1.408 1033 93
G00034 3 126 x 24 Ga. 0.06 0.095 10 1.207 1221 106
G00024 2 147 x 24 Ga. 0.06 0.095 8 1.25 1451 122
G00014 1 224 x 24 Ga. 0.08 0.095 8 1.528 2044 143
G00104 1/0 273 x 24 Ga. 0.08 0.095 6 1.619 2487 165
G00204 2/0 329 x 24 Ga. 0.08 0.095 6 1.737 2851 192
G00304 3/0 441 x 24 Ga. 0.08 0.095 4 1.894 3784 221
G00404 4/0 532 x 24 Ga. 0.08 0.095 4 2.029 4351 255