Philaflex Tray Cable
Application:
Commercial, Data Centers, & Industrial Installations for channels, ducts, wireways, TC-ER-JP rated indoor or outdoor cable trays, and raceways.
Features:
- ULTIMATE FLEXIBILITY - For easier and faster installation that saves time and labor burdened by stiff tray cable and tight bends.
- Sizes 8 AWG to 1000 MCM
- Sunlight Resistant
- Oil Resistant
- Abrasion Resistant
- For wet or dry locations
- Permitted for direct Burial.
- For applications requiring TC-ER-JP rating
- RoHS Compliant
- Made in the USA
Construction:
- Planetary cabling to prevent twisting and torsion of conductors for superior flexibility and durability.
- Soft annealed bare copper ASTM Class I - 24 AWG stranding for superior flexibility.
- Inners insulated with high dielectric strength +105C to -40C extra flexible PVC.
- Bare copper ground.
- Inners and ground cabled with clear spiral wrapped Mylar tape and Nylon rip cord for easy stripping.
- Jacketed with sun, flame, oil, & water, resistant +105C to -40C extra flexible black PVC.
- Color Code: ICEA Method 4 printed numbers - NEMA (K-2)
- Black Inners printed with white ink:1-Black, 2-Red, 3-Blue, 4-Orange
Standards:
ICEA S-73-532; ICEA S-95-
Philaflex Tray Cable Produts Table
Part Number | Size (AWG) | No. of Conductors | Ground Size | Jacket Thickness “ | Diameter Inches | Ampacity Amps | Weight Lbs./MFT |
TC8-3C | 8 | 3 | 10 | 0.06 | 0.653 | 55 | 342 |
TC8-4C | 8 | 4 | 10 | 0.06 | 0.717 | 55 | 417 |
TC6-3C | 6 | 3 | 8 | 0.08 | 0.868 | 75 | 553 |
TC6-4C | 6 | 4 | 8 | 0.08 | 0.952 | 75 | 689 |
TC4-3C | 4 | 3 | 8 | 0.08 | 0.988 | 95 | 774 |
TC4-4C | 4 | 4 | 8 | 0.08 | 1.09 | 95 | 980 |
TC3-3C | 3 | 3 | 6 | 0.08 | 1.05 | 115 | 947 |
TC3-4C | 3 | 4 | 6 | 0.08 | 1.155 | 115 | 1197 |
TC2-3C | 2 | 3 | 6 | 0.08 | 1.109 | 130 | 1088 |
TC2-4C | 2 | 4 | 6 | 0.08 | 1.223 | 130 | 1383 |
TC1-3C | 1 | 3 | 6 | 0.08 | 1.299 | 145 | 1408 |
TC1-4C | 1 | 4 | 6 | 0.08 | 1.435 | 145 | 1801 |
TC1-0-3C | 1/0 | 3 | 6 | 0.08 | 1.402 | 170 | 1637 |
TC1-0-4C | 1/0 | 4 | 6 | 0.08 | 1.551 | 170 | 2103 |
TC2-0-3C | 2/0 | 3 | 6 | 0.08 | 1.585 | 195 | 2097 |
TC2-0-4C | 2/0 | 4 | 6 | 0.11 | 1.861 | 195 | 2819 |
TC3-0-3C | 3/0 | 3 | 4 | 0.11 | 1.751 | 225 | 2632 |
TC3-0-4C | 3/0 | 4 | 4 | 0.11 | 1.935 | 225 | 3375 |
TC4-0-3C | 4/0 | 3 | 4 | 0.11 | 1.889 | 260 | 3183 |
TC4-0-4C | 4/0 | 4 | 4 | 0.11 | 2.08 | 260 | 4103 |
TC250-3C | 250 MCM | 3 | 4 | 0.11 | 2.102 | 290 | 3820 |
TC250-4C | 250 MCM | 4 | 4 | 0.11 | 2.328 | 290 | 4942 |
TC300-3C | 300 MCM | 3 | 3 | 0.11 | 2.221 | 320 | 4352 |
TC300-4C | 300 MCM | 4 | 3 | 0.11 | 2.461 | 320 | 5633 |
TC350-3C | 350 MCM | 3 | 3 | 0.11 | 2.356 | 350 | 5056 |
TC350-4C | 350 MCM | 4 | 3 | 0.11 | 2.613 | 350 | 6564 |
TC400-3C | 400 MCM | 3 | 3 | 0.11 | 2.423 | 380 | 5507 |
TC400-4C | 400 MCM | 4 | 3 | 0.11 | 2.688 | 380 | 7163 |
TC500-3C | 500 MCM | 3 | 2 | 0.11 | 2.66 | 430 | 6735 |
TC500-4C | 500 MCM | 4 | 2 | 0.14 | 3.013 | 430 | 8958 |
TC600-3C | 600 MCM | 3 | 2 | 0.14 | 2.97 | 475 | 8190 |
TC600-4C | 600 MCM | 4 | 2 | 0.14 | 3.293 | 475 | 10662 |
TC750-3C | 750 MCM | 3 | 2 | 0.14 | 3.419 | 535 | 10301 |
TC750-4C | 750 MCM | 4 | 2 | 0.14 | 3.795 | 535 | 13427 |
TC1000-3C | 1000 MCM | 3 | 1/0 | 0.14 | 3.832 | 615 | 13530 |
TC1000-4C | 1000 MCM | 4 | 1/0 | 0.14 | 4.259 | 615 | 17682 |
Ampacity is based on Ambient Temperature of 30°C (86°F) per NEC Table 310.15(B)(16).
When neutral conductor is considered current carrying, the ampacity of 4 conductor cables is reduced by a factor .80 per NEC 310.15(B)(3)(a)
Refer to NEC 310.15(B)(2) for the Ampacity correction factors where the ambient temperature is other than 30°C (86°F).
All dimensions and weights are nominal and approximate.